System components for rail mounting
KNX area / line coupler
rail mounting device, 2 rail units
ETS product family: System components
Product type: Line coupler
Function
The coupler connects two KNX data lines and ensures the electrical isolation between these lines. The definite functions of the device are defined by addressing and parameterisation.
Line coupler
Connection of a line with a main line. Alternatively with or without filter function. The coupler belongs logically to the subordinate line (here: line).
Area coupler
Connection of a main line and an area line. Alternatively with or without filter function. The coupler belongs logically to the subordinate line (here: main line).
Amplifier
Preparation and repetition of telegrams on a line, no filter function. Division of a line into max. 4 independent line segments (max. 3 line amplifiers connected in parallel per line). Each line segment requires a separate power supply including a choke.
ETS product family: System components
Product type: Line coupler
Function
The coupler connects two KNX data lines and ensures the electrical isolation between these lines. The definite functions of the device are defined by addressing and parameterisation.
Line coupler
Connection of a line with a main line. Alternatively with or without filter function. The coupler belongs logically to the subordinate line (here: line).
Area coupler
Connection of a main line and an area line. Alternatively with or without filter function. The coupler belongs logically to the subordinate line (here: main line).
Amplifier
Preparation and repetition of telegrams on a line, no filter function. Division of a line into max. 4 independent line segments (max. 3 line amplifiers connected in parallel per line). Each line segment requires a separate power supply including a choke.
-
Product information & Downloads
Reference number 2142 REG-01
-
Technical data
KNX medium: NaV Power supply: DC 21 ... 32 V from superordinate line Current consumption superordinate line: approx. 8 mA subordinate line: approx. 6 mA Connection mode: connection terminal Mounting: on DIN rail Ambient temperature: +23 ... +number,0} °F Storing temperature: −13 ... +number,0} °F Protection class: III acc. EN 61140 Mounting width: 1.42 in (2 rail units)